[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975380":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},975380,704,1,"单选题","报警阀组报警功能（以湿式报警阀警铃试验阀测试为例）的测试内容如下：①检查确认系统各管路阀门处于正常启闭状态②将消防泵组电气控制柜置于“手动”运行状态③打开警铃试验阀，同时按下秒表开始计时，待警铃响起时，停止秒表，通过秒表显示核查延迟时间，水力警铃应在5至90s内发出报警铃声④使用声级计测量，距水力警铃3m远处警铃声压级不应小于70dB⑤关闭警铃试验阀，观察水力警铃停动、余水排出后，恢复消防泵组电气控制柜为“自动”运行状态⑥设有消防控制室的还应核查信号反馈情况，测试完毕后进行复位操作⑦记录检查测试情况以下关于测试报警阀组报警功能的操作程序正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","③⑤④⑥⑦①②",false,{"key":16,"text":17,"correct":18},"B","①②③④⑤⑥⑦",true,{"key":20,"text":21,"correct":14},"C","①②④③⑤⑥⑦",{"key":23,"text":24,"correct":14},"D","③①④⑤⑥⑦②","测试报警阀组报警功能的操作程序：①检查确认系统各管路阀门处于正常启闭状态②将消防泵组电气控制柜置于“手动”运行状态③打开警铃试验阀，同时按下秒表开始计时，待警铃响起时，停止秒表，通过秒表显示核查延迟时间，水力警铃应在5至90s内发出报警铃声④使用声级计测量，距水力警铃3m远处警铃声压级不应小于70dB⑤关闭警铃试验阀，观察水力警铃停动、余水排出后，恢复消防泵组电气控制柜为“自动”运行状态⑥设有消防控制室的还应核查信号反馈情况，测试完毕后进行复位操作⑦记录检查测试情况",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]