[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975356":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},975356,704,1,"单选题","下列关于高位消防水箱最低有效水位应满足水灭火设施最不利点处的静水压力说法错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","一类高层公共建筑不应低于0.10MPa,但当建筑高度超过100m时，不应低于0.15MPa。",false,{"key":16,"text":17,"correct":14},"B","高层住宅、二类高层公共建筑、多层公共建筑不应低于0.07MPa,多层住宅不宜低于0.07MPa。",{"key":19,"text":20,"correct":14},"C","工业建筑不应低于0.10MPa,当建筑体积小于20000m3时，不宜低于0.07MPa。",{"key":22,"text":23,"correct":24},"D","自动喷水灭火系统等自动水灭火系统应根据喷头灭火需求压力确定，但最小不应小于0.15MPa。",true,"高位消防水箱的设置位置应高于其所服务的水灭火设施，且最低有效水位应满足水灭火设施最不利点处的静水压力，并应按下列规定确定：（1）一类高层公共建筑不应低于0.10MPa,但当建筑高度超过100m时，不应低于0.15MPa。（2）高层住宅、二类高层公共建筑、多层公共建筑不应低于0.07MPa,多层住宅不宜低于0.07MPa。（3）工业建筑不应低于0.10MPa,当建筑体积小于20000m3时，不宜低于0.07MPa。（4）自动喷水灭火系统等自动水灭火系统应根据喷头灭火需求压力确定，但最小不应小于0.10MPa。（5）当高位消防水箱不能满足前述静压要求时，应设稳压泵。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]