[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975288":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},975288,704,2,"多选题","下列关于消火栓系统最不利点处消火栓栓口的静压的说法错误的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","某建筑高度为164m的综合建筑最不利点处消火栓栓口的静压不应低于0.10MPa",true,{"key":16,"text":17,"correct":18},"B","建筑高度为32m的办公建筑，最不利点处消火栓栓口的静压不应低于0.07MPa",false,{"key":20,"text":21,"correct":14},"C","当工业建筑建筑体积为20000m3时，最不利点处消火栓栓口的静压不宜低于0.07MPa",{"key":23,"text":24,"correct":14},"D","采用稳压泵稳压时，最不利点处水灭火设施在准工作状态时的静水压力不应小于0.15MPa",{"key":26,"text":27,"correct":18},"E","多层住宅最不利点处消火栓栓口的静压不宜低于0.07MPa","ACD","最不利点处消火栓栓口的静压：一类高层公共建筑不应低于0.10MPa，当建筑高度超过100m时，不应低于0.15MPa；高层住宅、二类高层公共建筑、多层公共建筑，不应低于0.07MPa，多层住宅不宜低于0.07MPa；工业建筑不应低于0.10MPa，当建筑体积小于20000m3时，不宜低于0.07MPa。当采用稳压泵稳压时，最不利点处水灭火设施在准工作状态时的静水压力应大于0.15MPa。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]