[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975270":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},975270,704,1,"单选题","下列关于消防水池（水箱）的安装要求说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防水池的给水管应根据其有效容积和补水时间确定，补水时间不宜大于96h",true,{"key":16,"text":17,"correct":18},"B","防水池进水管管径应通过计算确定，且不应小于DN100",false,{"key":20,"text":21,"correct":18},"C","消防水箱进水管的管径应满足消防水箱8h充满水的要求，但管径不应小于DN32，进水管宜设置液位阀或浮球阀",{"key":23,"text":24,"correct":18},"D","消防水池（水箱）出水管或水泵吸水管应满足最低有效水位出水不掺气的技术要求","（1）消防水池的给水管应根据其有效容积和补水时间确定，补水时间不宜大于48h，当消防水池有效总容积大于2000m3时，不应大于96h。消防水池进水管管径应通过计算确定，且不应小于DN100。 （2）消防水箱进水管的管径应满足消防水箱8h充满水的要求，但管径不应小于DN32，进水管宜设置液位阀或浮球阀。高位消防水箱出水管管径应满足消防给水设计流量的出水要求，且不应小于DN100。 （3）消防水池（水箱）出水管或水泵吸水管应满足最低有效水位出水不掺气的技术要求。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]