[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975249":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},975249,704,1,"单选题","下列关于消防设备末端配电装置的安装位置说法不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防设备末端配电装置宜靠近用电设备安装",false,{"key":16,"text":17,"correct":18},"B","消防设备末端配电装置在墙上安装时，其底边距地（楼）面高度宜为1.5～1.8m",true,{"key":20,"text":21,"correct":14},"C","消防设备末端配电装置落地安装时，其底边宜高岀地（楼）面0.1～0.2m",{"key":23,"text":24,"correct":14},"D","控制器应安装牢固，不应倾斜","对照消防设计文件，检查消防设备末端配电装置（图5-3-1）的安装位置和数量： （1）消防设备末端配电装置宜靠近用电设备安装。 （2）消防设备末端配电装置在墙上安装时，其底边距地（楼）面高度宜为1.3～1.5m，其靠近门轴的侧面距墙不应小于0.5m，正面操作距离不应小于1.2m；落地安装时，其底边宜高岀地（楼）面0.1～0.2m。 （3）控制器应安装牢固，不应倾斜。安装在轻质墙上时，应采取加固措施。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]