[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975204":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},975204,704,2,"多选题","下列关于防火卷帘导轨的安装说法正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","导轨顶部应成圆弧形，其长度应保证卷帘正常运行",true,{"key":16,"text":17,"correct":14},"B","导轨的滑动面应光滑、平直",{"key":19,"text":20,"correct":21},"C","双帘面卷帘不同帘面的导轨也应互相平行，其平行度误差均不应大于2mm",false,{"key":23,"text":24,"correct":21},"D","卷帘的防烟装置与帘面应均匀紧密贴合，其贴合面长度不应小于导轨长度的70%",{"key":26,"text":27,"correct":21},"E","防火卷帘的导轨应安装在建筑结构上，并应采用预埋螺栓、焊接或膨胀螺栓连接。导轨安装应牢固，固定点间距应为600～8000mm","AB","防火卷帘导轨的安装： （1）导轨顶部应成圆弧形，其长度应保证卷帘正常运行； （2）防火卷帘帘板或帘面嵌入导轨的深度应符合表5-3-6的规定； （3）导轨的滑动面应光滑、平直。帘板或帘面、滚轮在导轨内运行时应平稳、顺畅，不应有碰撞和冲击现象； （4）单帘面卷帘的两根导轨应互相平行，双帘面卷帘不同帘面的导轨也应互相平行，其平行度误差均不应大于5mm； （5）卷帘的防烟装置与帘面应均匀紧密贴合，其贴合面长度不应小于导轨长度的80%； （6）防火卷帘的导轨应安装在建筑结构上，并应采用预埋螺栓、焊接或膨胀螺栓连接。导轨安装应牢固，固定点间距应为600～1000mm。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]