[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975188":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},975188,704,1,"单选题","下列关于室外消火栓的安装说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","室外消火栓的选型、规格、数量和位置应符合设计要求",false,{"key":16,"text":17,"correct":18},"B","地下消火栓井的直径不宜小于1.2m",true,{"key":20,"text":21,"correct":14},"C","地下消火栓顶部进水口或顶部出水口应正对井口，顶部进水口或顶部出水口与消防井盖底面的距离不应大于0.4m",{"key":23,"text":24,"correct":14},"D","室外地上消火栓安装时，消火栓顶距地面高为0.64m，各接口应便于连接和操作","室外消火栓安装要求： （1）室外消火栓的选型、规格、数量和位置应符合设计要求。 （2）地下消火栓井的直径不宜小于1.5m，当地下室外消火栓的取水口在冰冻线以上时，应采取保温措施；地下消火栓顶部进水口或顶部出水口应正对井口，顶部进水口或顶部出水口与消防井盖底面的距离不应大于0.4m；井内应有足够的操作空间，并应做好防水措施；地下室外消火栓应设置永久性固定标识。 （3）室外地上消火栓安装时，消火栓顶距地面高为0.64m，各接口应便于连接和操作；立管应垂直、稳固，控制阀门井距消火栓不应超过2.5m，消火栓弯管底部应设支墩或支座。。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]