[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975185":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},975185,704,1,"单选题","下列关于室外消火栓系统管网的安装要求的说法错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","埋地金属管道的最小管顶覆土不应小于0.70m",false,{"key":16,"text":17,"correct":14},"B","当在机动车道下时管道最小管顶覆土应经计算确定，且不应小于0.90m",{"key":19,"text":20,"correct":21},"C","埋地金属管道最小管顶覆土应至少在冰冻线以下0.20m",true,{"key":23,"text":24,"correct":14},"D","埋地管道采用钢丝网骨架塑料复合管时，其最小管顶覆土深度，在人行道下不应小于0.80m，且应在冰冻线下0.3m","室外消火栓系统管网的安装要求： （1）埋地金属管道的最小管顶覆土不应小于0.70m；当在机动车道下时管道最小管顶覆土应经计算确定，且不应小于0.90m；管道最小管顶覆土应至少在冰冻线以下0.30m。 （2）埋地管道采用钢丝网骨架塑料复合管时，其最小管顶覆土深度，在人行道下不应小于0.80m，在轻型车行道下不应小于1.0m，且应在冰冻线下0.3m；在重型汽车道路或铁路、高速公路下应设置保护套管，套管与钢丝网骨架塑料复合管的净距不应小于100mm。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]