[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975154":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},975154,704,2,"多选题","下列关于自动喷水灭火系统联动控制的测试方法自动喷水灭火系统测试方法描述正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","通过开启末端试水装置、报警阀泄水阀、警铃试验阀、专用测试管路或报警阀压力开关、压力开关配用输入模块模拟等方式产生报警阀压力开关动作信号",true,{"key":16,"text":17,"correct":14},"B","通过使用火灾探测器测试装置触发该报警阀所在防护区域内任一火灾探测器或启动任一手动火灾报警按钮产生报警信号",{"key":19,"text":20,"correct":21},"C","通过使用火灾探测器测试装置触发该报警阀所在建筑内任一火灾探测器或启动任一手动火灾报警按钮产生报警信号",false,{"key":23,"text":24,"correct":14},"D","在接到压力开关动作信号和报警信号后，消防联动控制器发出消防水泵启动信",{"key":26,"text":27,"correct":14},"E","通过开启警铃试验阀，直接驱动压力开关动作并启动消防水泵。","ABDE","联动控制的测试方法： （1）通过开启末端试水装置、报警阀泄水阀、警铃试验阀、专用测试管路或报警阀压力开关、压力开关配用输入模块模拟等方式产生报警阀压力开关动作信号。 （2）通过使用火灾探测器测试装置触发该报警阀所在防护区域内任一火灾探测器或启动任一手动火灾报警按钮产生报警信号。 （3）在接到上述两个信号后，消防联动控制器发出消防水泵启动信号。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]