[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975149":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},975149,704,1,"单选题","对于湿式、干式自动喷水灭火系统，消防联动控制器在收到（ ）信号后不能发出启泵信号。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","报警阀组压力开关发出的反馈信号和该报警阀防护区内任一感烟火灾探测器的信号",false,{"key":16,"text":17,"correct":14},"B","报警阀组压力开关发出的反馈信号和该报警阀防护区内任一感温火灾探测器的信号",{"key":19,"text":20,"correct":14},"C","报警阀组压力开关发出的反馈信号和该报警阀防护区内手动火灾报警按钮的信号",{"key":22,"text":23,"correct":24},"D","该报警阀防护区内两个独立的火灾报警信号",true,"联动控制的测试方法： （1）通过开启末端试水装置、报警阀泄水阀、警铃试验阀、专用测试管路或报警阀压力开关、压力开关配用输入模块模拟等方式产生报警阀压力开关动作信号。 （2）通过使用火灾探测器测试装置触发该报警阀所在防护区域内任一火灾探测器或启动任一手动火灾报警按钮产生报警信号。 （3）在接到上述两个信号后，消防联动控制器发出消防水泵启动信号。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]