[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975126":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":17,"analysis":19},975126,704,3,"判断题","干式系统充气连接管接口应在报警阀气室充注水位以上部位，且充气连接管的直径不应小于25mm。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",false,{"key":16,"text":17,"correct":18},"B","错误",true,"干式系统充气连接管接口应在报警阀气室充注水位以上部位，且充气连接管的直径不应小于15mm。",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]