[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975115":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},975115,704,2,"多选题","下列关于报警阀组的安装说法正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","报警阀距地面的高度为1.2m",true,{"key":16,"text":17,"correct":18},"B","报警阀两侧与墙的距离为300mm",false,{"key":20,"text":21,"correct":18},"C","报警阀正面与墙的距离为1.0m",{"key":23,"text":24,"correct":14},"D","报警阀组凸出部位之间的距离为800mm",{"key":26,"text":27,"correct":14},"E","设置报警阀组的部位应设有排水设施","ADE","报警阀组宜设在安全及易于操作的地点，报警阀距地面的高度宜为1.2m。两侧与墙的距离不应小于0.5m，正面与墙的距离不应小于1.2m，报警阀组凸出部位之间的距离不应小于0.5m。设置报警阀组的部位应设有排水设施，排水能力应满足报警阀调试、验收和利用试水阀门泄空系统管道的要求。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]