[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975109":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},975109,704,1,"单选题","下列关于干式系统的设置说法不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","干式系统充气连接管接口应在报警阀气室充注水位以上部位，且充气连接管的直径不应小于25mm",true,{"key":16,"text":17,"correct":18},"B","止回阀、截止阀应安装在充气连接管上",false,{"key":20,"text":21,"correct":18},"C","低气压预报警装置应安装在配水干管一侧",{"key":23,"text":24,"correct":18},"D","空气压缩机的气泵和储气罐、加速器上应安装压力表","干式系统充气连接管接口应在报警阀气室充注水位以上部位，且充气连接管的直径不应小于15mm；止回阀、截止阀应安装在充气连接管上；安全排气阀应安装在气源与报警阀之间，且应靠近报警阀；加速器应安装在靠近报警阀的位置，且应有防止水进入加速器的措施；低气压预报警装置应安装在配水干管一侧；空气压缩机的气泵和储气罐、加速器上应安装压力表。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]