[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975097":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},975097,704,3,"判断题","本区域内无需要手动控制的消防联动设备时，集中报警系统和控制中心报警系统中的区域火灾报警控制器可设置在无人值班的场所。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"集中报警系统和控制中心报警系统中的区域火灾报警控制器在满足下列条件时，可设置在无人值班的场所：（1）本区域内无需要手动控制的消防联动设备。（2）本火灾报警控制器的所有信息在集中火灾报警控制器上均有显示，且能接收起集中控制功能的火灾报警控制器的联动控制信号，并自动启动相应的消防设备。（3）设置的场所只有值班人员可以进入。",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]