[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975076":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},975076,704,1,"单选题","下列关于火灾警报器的设置和安装要求说法不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","火灾警报器应设置在每个楼层的楼梯口、消防电梯前室、建筑内部拐角等处的明显部位，且不宜与安全出口指示标志灯具设置在同一面墙上",false,{"key":16,"text":17,"correct":14},"B","每个报警区域内应均匀设置火灾警报器，其声压级不应小于60dB",{"key":19,"text":20,"correct":14},"C","在环境噪声大于60dB的场所，其声压级应高于背景噪声15dB",{"key":22,"text":23,"correct":24},"D","当火灾警报器采用壁挂方式安装时，底边距地面高度不应小于2.2m",true,"火灾警报器的设置和安装要求： （1）火灾警报器应设置在每个楼层的楼梯口、消防电梯前室、建筑内部拐角等处的明显部位，且不宜与安全出口指示标志灯具设置在同一面墙上。 （2）每个报警区域内应均匀设置火灾警报器，其声压级不应小于60dB；在环境噪声大于60dB的场所，其声压级应高于背景噪声15dB。 （3）当火灾警报器采用壁挂方式安装时，底边距地面高度应大于2.2m。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]