[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975043":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},975043,704,2,"多选题","消防控制室远程不能启停消防水泵的原因包括（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","专用线路开路或断路",true,{"key":16,"text":17,"correct":14},"B","多线控制盘损坏",{"key":19,"text":20,"correct":14},"C","多线控制盘配用的切换模块线路发生故障",{"key":22,"text":23,"correct":24},"D","防泵组电气控制柜处于“自动”状态",false,{"key":26,"text":27,"correct":14},"E","多线控制盘未解锁处于“手动禁止”状态","ABCE","消防控制室远程不能启停消防水泵的原因：（1）专用线路开路或断路（2）多线控制盘按钮接触不良或多线控制盘线路松动、多线控制盘损坏（3）多线控制盘配用的切换模块线路发生故障或模块损坏（4）多线控制盘未解锁处于“手动禁止”状态，或消防泵组电气控制柜处于“手动”状态。故D不是故障原因。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]