[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-975017":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},975017,704,2,"多选题","消防应急照明和疏散指示系统中主电故障报警的检查项目（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","检查输入电源是否完好",true,{"key":16,"text":17,"correct":14},"B","检查接触是否不良",{"key":19,"text":20,"correct":21},"C","检查蓄电池是否有损坏",false,{"key":23,"text":24,"correct":21},"D","检查蓄电池端子是否接触良好",{"key":26,"text":27,"correct":21},"E","检查蓄电池端子接线是否正确","AB","消防应急照明和疏散指示系统中主电故障报警检查输入电源是否完好，交流电源电压是否为180~250V，检查主电熔丝有熔断，若已熔断，应更换满足要求的熔丝；检查接触是否不良等，若接线端子或接头松动，应重新连接紧固；若接头处有氧化或锈蚀痕迹，可断开接点，用细砂纸磨掉或用电工刀刮掉氧化层，镀锡和涂抹凡士林后，再重新连接紧固。故选AB。CDE是备电故障报警的检查项目。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]