[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974986":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},974986,704,1,"单选题","更换干式报警阀阀瓣密封圈的注意事项中的“减损失”是指（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","防止因消防水泵意外启动而造成不必要的损失",false,{"key":16,"text":17,"correct":18},"B","更换作业应尽量减少管网用水的排放量",true,{"key":20,"text":21,"correct":14},"C","关闭阀门时尽可能选择距离被更换件最近的阀门",{"key":23,"text":24,"correct":14},"D","减少人员伤亡","更换干式报警阀阀瓣密封圈的注意事项：1.根据拟更换组件所处位置及其对系统运行的影响程度，按照防误动、减损失、控范围的原则，制定维修方案和安全管理措施。（1）防误动。通过采取关闭必要的阀门，调整水泵控制、联动控制为手动状态等措施，防止因消防水泵意外启动而造成不必要的损失。（2）减损失。更换作业应尽量减少管网用水的排放量，能不排水的尽量不排水，必须排水的通过阀门控制减少排放量，避免放空系统侧管网全部用水。（故选B）（3）控范围。关闭阀门时尽可能选择距离被更换件最近的阀门。例如，对配水支管上组件更换，仅需关闭该分区水流指示器前的控制阀；系统中有多个报警阀组的，受影响范围也应控制在需更换组件的报警阀控制区域内。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]