[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974960":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},974960,704,3,"判断题","与多线控制盘配套用的切换模块线路发生故障或模块损坏，消防控制室不能远程手动启停风机。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"故障现象：消防控制室不能远程手动启停风机原因分析：（1）专用线路发生故障（2）多线控制盘按钮接触不良或多线控制盘损坏（3）与多线控制盘配套用的切换模块线路发生故障或模块损坏（4）多线控制盘未解锁处于“手动禁止”状态，或风机控制柜处于“手动”状态（5）风机及控制柜发生故障",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]