[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974897":3},{"question":4,"library":29},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":27,"analysis":28},974897,704,2,"多选题","下列属于消火栓出水压力不足的故障维修方法的是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","逐段排查渗漏部位并予以维修",true,{"key":16,"text":17,"correct":14},"B","消防水泵如存在供电故障及时予以维修",{"key":19,"text":20,"correct":14},"C","关闭试水管路阀门",{"key":22,"text":23,"correct":14},"D","排查起跳原因，泄压阀损坏的，维修和更换",{"key":25,"text":26,"correct":14},"E","重新设定启停泵压力","ABCDE","消火栓出水压力不足的故障维修方法： （1）逐段排查渗漏部位并予以维修； （2）启动消防水泵，如存在供电故障、消防水泵故障等，及时予以维修； （3）消防水泵进出水管路阀门应保持全开，并以铅封锁链锁定状态； （4）关闭试水管路阀门； （5）排查起跳原因，泄压阀损坏的，维修或更换；起跳压力设定不正确的，重新设定； （6）重新设定启停泵压力，稳压设施损坏的及时维修。",{"id":6,"name":30,"category":31,"favorite":32},"中级技能","建筑工程",0]