[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974896":3},{"question":4,"library":29},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":27,"analysis":28},974896,704,2,"多选题","下列属于消火栓出水压力不足的故障原因是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","临时高压系统消防水泵未启动",true,{"key":16,"text":17,"correct":14},"B","消防水泵出水管路阀门未完全开启",{"key":19,"text":20,"correct":14},"C","消防水泵试水管路阀门被误开启",{"key":22,"text":23,"correct":14},"D","出水管路泄压阀起跳泄水",{"key":25,"text":26,"correct":14},"E","设置的稳压设施压力设定不正确","ABCDE","故障现象：消火栓出水压力不足。原因分析：管网渗漏严重；临时高压系统消防水泵未启动；消防水泵出水管路阀门未完全开启；消防水泵试水管路阀门被误开启；出水管路泄压阀起跳泄水；设有稳压设施的，压力设定不正确或稳压设施损坏。维修方法：逐段排查渗漏部位井予以维修；启动消防水泵，如存在供电故障、消防水泵故障等，及时予以维修；消防水泵进出水管路阀门应保持全开，并以铅封锁链锁定状态；关闭试水管路阀门；排查起跳原因，泄压阀损坏的，维修和更换；起跳压力设定不正确的，重新设定；重新设定起停泵压力，稳压设施损坏的及时维修。",{"id":6,"name":30,"category":31,"favorite":32},"中级技能","建筑工程",0]