[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974825":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974825,704,2,"多选题","下列属于总线控制盘不能远程手动启动风阀（不包括未设电动开启功能的排烟防火阀）故障维修方法的是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","消防联动控制调整到“手动允许”状态",true,{"key":16,"text":17,"correct":14},"B","更换控制模块或检修线路",{"key":19,"text":20,"correct":14},"C","维修或更换键盘板",{"key":22,"text":23,"correct":14},"D","排除风阀故障",{"key":25,"text":26,"correct":27},"E","检查触发信号，满足与逻辑",false,"ABCD","故障现象：总线控制盘不能远程手动启动风阀（不包括未设电动开启功能的排烟防火阀）：原因分析 （1）消防联动控制为“手动禁止”状态； （2）控制模块或线路发生故障； （3）总线控制盘键盘板发生故障； （4）风阀发生故障。 维修方法： （1）消防联动控制调整到“手动允许”状态； （2）更换控制模块或检修线路； （3）维修或更换键盘板； （4）排除风阀故障。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]