[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974744":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},974744,704,3,"判断题","若消防总线联动控制未设定在“自动”状态或输出模块损坏，系统测试时，消防水泵不能自动启动。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"故障现象：系统测试时，消防水泵不能自动启动。原因分析：（1）压力开关设定值不正确或损坏；（2）消防泵组电气控制柜的控制模式未设定在“自动”状态或控制回路、电气部件发生故障；（3）消防总线联动控制未设定在\"自动”状态或输出模块损坏。",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]