[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974742":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":17,"analysis":19},974742,704,3,"判断题","电路接线脱落、复位弹簧损坏是末端试水装置测试时，水流指示器不动作，或关闭末端试水装置后，水流指示器反馈信号仍然显示为动作信号的原因。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",false,{"key":16,"text":17,"correct":18},"B","错误",true,"故障现象；末端试水装置测试时，水流指示器不动作，或关闭末端试水装置后，水流指示器反馈信号仍然显示为动作信号。原因分析：（1）浆片被管腔内杂物卡阻；（2）调整螺母与触头未调试到位；（3）电路接线脱落；（4）复位弹簧损坏。维修方法：（1）清除水流指示器管腔内的异物；（2）将调整螺母与触头调试到位；（3）检查并接实脱落线路；（4）维修和更换复位弹簧。",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]