[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974740":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974740,704,2,"多选题","下列属于干式报警阀迟动作或不动作的原因是（ ）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","保持底水在正常水位",true,{"key":16,"text":17,"correct":14},"B","进一步排查水源侧压力不足原因并进行维修",{"key":19,"text":20,"correct":14},"C","安装或更换加速器并进行调试",{"key":22,"text":23,"correct":24},"D","检查阀瓣密封处渗漏原因",false,{"key":26,"text":27,"correct":24},"E","供气装置发生故障","ABC","故障现象：干式报警阀迟动作或不动作。原因分析： （1）底水加注过高，阀瓣承受额外的水柱静压，导致干式报警阀迟动作； （2）水源侧压力不足，导致干式报警阀迟开； （3）系统管网容积较大，未设加速器或加速器损坏。 维修方法： （1）打开冷凝水排水阀，保持底水在正常水位； （2）进一步排查水源侧压力不足原因并进行维修； （3）安装或更换加速器并进行调试。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]