[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974731":3},{"question":4,"library":25},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":23,"analysis":24},974731,704,2,"多选题","下列属于干式报警阀误动作的可能原因是（ ）。 A.阀瓣密封处渗漏严重 B.未定期检查和加注底水 C.供气装置发生故障 D.系统侧管网发生不正常漏气",[11,14,16,18,20],{"key":12,"text":12,"correct":13},"A",true,{"key":15,"text":15,"correct":13},"B",{"key":17,"text":17,"correct":13},"C",{"key":19,"text":19,"correct":13},"D",{"key":21,"text":21,"correct":22},"E",false,"ABCD","干式报警阀误动作的原因： （1）阀瓣密封处渗漏严重，失去底水后漏气，系统侧气压下降，发生误动作； （2）未定期检查和加注底水，底水长时间渗漏后漏气，系统气压下降而使阀瓣误动作； （3）供气装置发生故障，造成系统侧气压低于其最小供气压力，使干式报警阀误动作； （4）系统侧管网发生不正常漏气，造成系统侧气压低于其最小供气压力，使干式报警阀误动作。",{"id":6,"name":26,"category":27,"favorite":28},"中级技能","建筑工程",0]