[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974726":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},974726,704,1,"单选题","下列不属于干式报警阀误动作原因的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","阀瓣密封处渗漏严重",false,{"key":16,"text":17,"correct":18},"B","底水加注过高",true,{"key":20,"text":21,"correct":14},"C","供气装置发生故障",{"key":23,"text":24,"correct":14},"D","系统侧管网发生不正常漏气","故障现象：干式报警阀误动作。原因分析： （1）阀瓣密封处渗漏严重，失去底水后漏气，系统测气压下降发生误动作； （2）未定期检查和加注底水，底水长时间渗漏后漏气，系统气压下降而使阀瓣误动作； （3）供气装置发生故障，造成系统测气压低于其最小供气压力，使干式报警阀误动作； （4）系统侧管网发生不正常漏气，造成系统测气压低于其最小供气压力，使干式报警阀误动作。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]