[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974718":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},974718,704,1,"单选题","下列不属于末端试水装置测试时，水流指示器不动作维修方法的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","消除水流指示器管腔内的异物",false,{"key":16,"text":17,"correct":14},"B","将调整螺母与触头调试到位",{"key":19,"text":20,"correct":21},"C","排查系统侧管网渗漏点并进行维修",true,{"key":23,"text":24,"correct":14},"D","维修和更换复位弹簧","故障现象：末端试水装置测试时，水流指示器不动作，或关闭末端试水装置后，水流指示器反馈信号仍然显示为动作信号。原因分析： （1）浆片被管腔内杂物卡阻； （2）调整螺母与触头未调试到位； （3）电路接线脱落； （4）复位弹簧损坏。 维修方法： （1）消除水流指示器管腔内的异物； （2）将调整螺母与触头调试到位； （3）检查并接实脱落线路； （4）维修和更换复位弹簧。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]