[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974712":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},974712,704,3,"判断题","消防泵组电气控制柜处于“手动”状态，消防控制室远程不能启停消防水泵",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"故障现象：消防控制室远程不能启停消防水泵。原因分析：（1）专用线路开路或断路；（2）多线控制盘按钮接触不良或多线控制盘线路松动、多线控制盘损坏；（3）多线控制盘配用的切换模块线路发生故障或模块损坏；（4）多线控制盘未解锁，处于“手动禁止”状态或消防泵组电气控制柜处于“手动”状态",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]