[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974709":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":17,"analysis":19},974709,704,3,"判断题","干式报警阀误动作一般是阀瓣密封处渗漏严重，失去底水后漏气，系统测气压下降发生误动作。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",false,{"key":16,"text":17,"correct":18},"B","错误",true,"干式报警阀误动作。原因分析：（1）阀瓣密封处渗漏严重，失去底水后漏气，系统测气压下降发生误动作；（2）未定期检查和加注底水，底水长时间渗漏后漏气，系统气压下降而使阀瓣误动作；（3）供气装置发生故障，造成系统测气压低于其最小供气压力，使干式报警阀误动作：（4）系统侧管网发生不正常漏气，造成系统测气压低于其最小供气压力，使干式报警阀误动作。",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]