[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974707":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":17,"analysis":19},974707,704,3,"判断题","止回阀安装方向错误会导致消防水泵结合器过水能力不足。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",false,{"key":16,"text":17,"correct":18},"B","错误",true,"故障现象：消防水泵结合器过水能力不足。原因分析：（1）连接处密封不严、损坏或管道损坏、渗漏严重。（2）止回阀粘连，开启度不够。（3）安全阀选型不当或损坏，起跳泄水。（4）控制阀未完全关闭。（5）放水阀被误开启。（6）设备和管道内有杂物。",{"id":6,"name":21,"category":22,"favorite":23},"中级技能","建筑工程",0]