[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974696":3},{"question":4,"library":29},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":27,"analysis":28},974696,704,2,"多选题","下列关于稳压泵不能正常启动的维修方法正确的是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","根据设计值重新设定稳压泵启泵压力",true,{"key":16,"text":17,"correct":14},"B","检测和调整压力信号开关控制，使正常启闭，不能修复的予以更换",{"key":19,"text":20,"correct":14},"C","逐一检查控制模块，采用其他方式启动稳压泵，核定问题模块，予以修复或更换",{"key":22,"text":23,"correct":14},"D","将控制模式设定为自动状态",{"key":25,"text":26,"correct":14},"E","灭火后手动恢复稳压泵处于正常控制状态","ABCDE","稳压泵不能正常启动的维修方法包括： （1）根据设计值重新设定稳压泵启泵压力； （2）检测和调整压力信号开关控制使正常启闭，不能修复的予以更换； （3）逐一检查控制模块，釆用其他方式启动稳压泵，核定问题模块，予以修复或更换； （4）将控制模式设定为“自动”状态； （5）灭火后手动恢复稳压泵处于正常控制状态。",{"id":6,"name":30,"category":31,"favorite":32},"中级技能","建筑工程",0]