[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974694":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974694,704,2,"多选题","消防水池（水箱）液位显示装置无法显示液位的故障原因是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","未安装就地液位显示装置",true,{"key":16,"text":17,"correct":14},"B","玻璃管液位计进水管被误关闭，排水管被误打开，浮子损坏或被异物卡住",{"key":19,"text":20,"correct":14},"C","水位信号装置损坏、线路损坏",{"key":22,"text":23,"correct":24},"D","通气管、溢流管管口防虫网损坏",false,{"key":26,"text":27,"correct":24},"E","水箱出水管止回阀安装有误或损坏","ABC","故障现象：消防水池（水箱）液位显示装置无法显示液位。原因分析： （1）未安装就地液位显示装置。 （2）玻璃管液位计进水管被误关闭，排水管被误打开，浮子损坏或被异物卡住。 （3）水位信号装置损坏、线路损坏。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]