[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974688":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},974688,704,1,"单选题","下列不属于关闭末端试水装置后，水流指示器反馈信号仍然显示为动作信号的故障原因是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","浆片被管腔内杂物卡阻",false,{"key":16,"text":17,"correct":18},"B","系统管网漏水",true,{"key":20,"text":21,"correct":14},"C","电路接线脱落",{"key":23,"text":24,"correct":14},"D","复位弹簧损坏","故障现象：末端试水装置测试时，水流指示器不动作，或关闭末端试水装置后，水流指示器反馈信号仍然显示为动作信号。原因分析； （1）浆片被管腔内杂物卡阻； （2）调整螺母与触头未调试到位； （3）电路接线脱落； （4）复位弹簧损坏。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]