[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974685":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},974685,704,1,"单选题","下列不属于消防水泵结合器过水能力不足的原因是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","连接处管道损坏、渗漏严重",false,{"key":16,"text":17,"correct":14},"B","放水阀被误开启",{"key":19,"text":20,"correct":14},"C","设备和管道内有杂物",{"key":22,"text":23,"correct":24},"D","止回阀安装方向错误",true,"故障现象；消防水泵结合器过水能力不足。原因分析： （1）连接处密封不严、损坏或管道损坏、渗漏严重。 （2）止回阀粘连，开启度不够。 （3）安圈阀选型不当或损坏，起跳泄水。 （4）控制阀未完全关闭。 （5）放水阀被误开启。 （6）设备和管道内有杂物。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]