[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974674":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},974674,704,1,"单选题","下列不属于消防水池（水箱）液位报警处理办法的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","维修和更换浮球阀、液位控制阀",false,{"key":16,"text":17,"correct":14},"B","排查液位过低原因并进行维修",{"key":19,"text":20,"correct":21},"C","防腐、除锈，并对渗漏部位进行堵漏",true,{"key":23,"text":24,"correct":14},"D","重新设定报警液位","故障现象：消防水池（水箱）液位报警。原因分析： （1）浮球阀或液位控制阀产品存在质量问题，无法关闭。 （2）液位过低。 （3）液位报警装置发生报警故障。 （4）报警液位设定不准确。 维修方法： （1）维修和更换浮球阀、液位控制阀。 （2）排查液位过低原因并进行维修。 （3）维修或更换液位报警装置。 （4）重新设定报警液位。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]