[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974630":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974630,704,2,"多选题","关于消防设备末端配电装置的保养方法，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","配电装置断电后，用电动吹风或小毛刷等清洁柜中灰尘",true,{"key":16,"text":17,"correct":14},"B","检查断路器操作机构是否到位，接线螺栓是否紧固",{"key":19,"text":20,"correct":21},"C","如接触器触点磨损至原厚度的2\u002F3，应更换触点",false,{"key":23,"text":24,"correct":14},"D","检查电源指示仪表、指示灯应完好",{"key":26,"text":27,"correct":14},"E","清洁消防设备末端配电装置前应停电","ABDE","消防设备末端配电装置的保养方法：（1）清洁消防设备末端配电装置前应停电。（2）配电装置断电后，用电动吹风或小毛刷等清洁柜中灰尘，检查母线及引线连接是否良好、接点有无发热变色，检查电缆头、接线头是否牢固可靠，检查要求。（3）检查断路器操作机构是否到位，接线螺栓是否紧固。（4）清除接触器触点表面及四周的污物，检查接触器触点接触是否完好，如触点接触不良，必要时可稍微修锉触点表面，如触点严重烧蚀（触点磨损至原厚度的1\u002F3）应更换触点。（故C不正确）（5）检查电源指示仪表、指示灯应完好。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]