[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974626":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},974626,704,1,"单选题","消防电话系统保养操作程序的最后一个步骤是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","接通消防电话总机电源，使消防电话处于正常监视状态",false,{"key":16,"text":17,"correct":14},"B","保养完成后，对消防电话总机进行复位和自检操作，等待2min，观察消防电话主机是否处于正常监视状态",{"key":19,"text":20,"correct":21},"C","填写《建筑消防设施维护保养记录表》",true,{"key":23,"text":24,"correct":14},"D","功能检查","消防电话系统保养操作程序：步骤1接通消防电话总机电源，使消防电话处于正常监视状态。步骤2外观检查保养。用吸尘器、清洁的干软布等清除机壳、电话机表面、电话插孔内及所有接线端子处的灰尘。对所有按键进行按下、弹起操作。步骤3接线检查保养。用螺丝刀紧固接线端子，对锈蚀的接线端烫锡。步骤4功能检查。在消防控制室进行总机与所有消防电话分机、电话插孔之间互相呼叫与通话，呼叫铃声、通话应语音清晰，无振鸣。总机显示每部分机或电话插孔的位置，总机自检、消音、复位以及群呼、录音、记录和显示等功能完好。步骤5保养完成后，对消防电话总机进行复位和自检操作，等待2min，观察消防电话主机是否处于正常监视状态。步骤6填写《建筑消防设施维护保养记录表》。（故选C）",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]