[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974508":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},974508,704,1,"单选题","关于机械加压送风系统的控制，下列说法错误的是（ ）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","系统中任一常闭加压送风口开启时，加压风机应能自动启动。",false,{"key":16,"text":17,"correct":14},"B","加压送风机应能现场手动启动、通过火灾自动报警系统自动启动、消防控制室手动启动",{"key":19,"text":20,"correct":21},"C","当防火分区内火灾确认后，应开启该防火分区楼梯间的全部加压送风机和前室的常闭送风口。",true,{"key":23,"text":24,"correct":14},"D","当防火分区内火灾确认后，应能在15s内联动开启常闭加压送风口和加压送风机","加压送风机的启动应符合下列规定：1现场手动启动；2通过火灾自动报警系统自动启动；3消防控制室手动启动；4系统中任一常闭加压送风口开启时，加压风机应能自动启动。AB正确；当防火分区内火灾确认后，应能在15s内联动开启常闭加压送风口和加压送风机。并应符合下列规定：1应开启该防火分区楼梯间的全部加压送风机；2应开启该防火分区内着火层及其相邻上下层前室及合用前室的常闭送风口，同时开启加压送风机。C错误，D正确。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]