[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974410":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974410,704,2,"多选题","下列关于消防应急广播主机、功放机的工作状态指示灯功能描述正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","当输出功率大于额定功率120%并持续3s后，过载指示灯点亮",false,{"key":16,"text":17,"correct":14},"B","当内部品体管温度超过设定温度极限（100℃）6s后发生过温故障，指示灯常亮",{"key":19,"text":20,"correct":21},"C","监听打开时监听灯常亮，关闭熄灭",true,{"key":23,"text":24,"correct":21},"D","消音灯平时熄灭，有故障时按下消音键常亮",{"key":26,"text":27,"correct":21},"E","对指示器件和报警声器件进行检查，按下自检灯常亮，检查完毕熄灭","CDE","消防应急广播主机、功放机的工作状态指示灯功能： （1）电源灯：电源接入时，电源指示灯点亮； （2）过载灯：当输出功率大于额定功率120%并持续2s后，过载指示灯点亮； （3）过温灯：当内部品体管温度超过设定温度极限（90℃）6s后发生过温故限，指示灯常亮； （4）监听灯：监听打开时常亮，关闭熄灭； （5）消音灯：平时熄灭，有故障时按下消音键常亮； （6）自检灯：对指示器件和报警声器件进行检查，按下常亮，检查完毕熄灭；",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]