[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974406":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},974406,704,1,"单选题","下列关于消防电梯紧急迫降按钮设置要求不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","在消防员入口层（一般为首层）的电梯前室内设置供消防员专用的操作按钮",false,{"key":16,"text":17,"correct":14},"B","通常设有保护装置",{"key":19,"text":20,"correct":14},"C","按钮应设置在距消防电梯水平距离2m以内的墙面上",{"key":22,"text":23,"correct":24},"D","按钮应设置在距地面高度1.5～1.8m的墙面上",true,"消防电梯紧急迫降按钮设置要求：消防电梯应在消防员入口层（一般为首层）的电梯前室内设置供消防员专用的操作按钮（也称消防员开关、消防电梯开关），为防止非火灾情况下的人员误动通常设有保护装置。该按钮应设置在距消防电梯水平距离2m以内、距地面高度1.8～2.1m的墙面上。按钮动作后，消防电梯按预设逻辑转入消防工作状态。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]