[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974394":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},974394,704,1,"单选题","下列关于机械排烟系统与火灾自动报警系统联动作为排烟口、排烟窗或排烟阀开启的联动触发信号的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","由同一防烟分区内的两只独立火灾探测器的报警信号",true,{"key":16,"text":17,"correct":18},"B","由同一防火分区内的两只独立火灾探测器的报警信号",false,{"key":20,"text":21,"correct":18},"C","由防火分区内一只感温火灾探测器与一只感烟火灾探测器的报警信号",{"key":23,"text":24,"correct":18},"D","由防烟分区内一只火灾探测器与一只手动火灾报警按钮的报警信号","（1）机械排烟系统应与火灾自动报警系统联动，由同一防烟分区内的两只独立火灾探测器的报警信号作为排烟口、排烟窗或排烟阀开启的联动触发信号，并由消防联动控制器联动控制排烟口、排烟窗或排烟阀的开启，同时停止该防烟分区的空气调节系统。 （2）由排烟口、排烟窗或排烟阀开启的动作信号作为排烟风机启动的联动触发信号，并由消防联动控制器联动控制排烟风机的启动。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]