[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974347":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974347,704,2,"多选题","应急照明控制器在消防控制室地面上设置时，应符合下列规定：（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","单列布置时设备面板前的操作距离为1.5m",true,{"key":16,"text":17,"correct":18},"B","在值班人员经常工作的一面，设备面板至墙的距离不应小于3m",false,{"key":20,"text":21,"correct":18},"C","设备面板后的维修距离不宜小于2m",{"key":23,"text":24,"correct":14},"D","设备面板的排列长度大于4m时，其两端应设置宽度不小于1m的通道",{"key":26,"text":27,"correct":14},"E","双列布置时设备面板前的操作距离为1.5m","ADE","应急照明控制器在消防控制室地面上设置时，应符合下列规定： （1）设备面板前的操作距离，单列布置时不应小于1.5m，双列布置时不应小于2m； （2）在值班人员经常工作的一面，设备面板至墙的距离不应小于3m。 （3）设备面板后的维修距离不宜小于1m。 （4）设备面板的排列长度大于4m时，其两端应设置宽度不小于1m的通道。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]