[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974340":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974340,704,2,"多选题","下列关于疏散通道上设置的防火卷帘自动控制的说法正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","任一只专门用于联动防火卷帘的感温火灾探测器的报警信号联动控制防火卷帘下降至距楼板面1.8m处",false,{"key":16,"text":17,"correct":14},"B","任一只专门用于联动防火卷帘的感烟火灾探测器联动控制防火卷帘下降到楼板面",{"key":19,"text":20,"correct":21},"C","任一只专门用于联动防火卷帘的感温火灾探测器的报警信号联动控制防火卷帘下降到楼板面",true,{"key":23,"text":24,"correct":21},"D","任一只专门用于联动防火卷帘的感烟火灾探测器联动控制防火卷帘下降至距楼板面1.8m处",{"key":26,"text":27,"correct":14},"E","两只专门用于联动防火卷帘的感烟火灾探测器联动控制防火卷帘下降到楼板面","CD","对于疏散通道上设置的防火卷帘，由防火分区内任两只独立的感烟火灾探测器或任一只专门用于联动防火卷帘的感烟火灾探测器的报警信号联动控制防火卷帘下降至距楼板面1.8m处；由任一只专门用于联动防火卷帘的感温火灾探测器的报警信号联动控制防火卷帘下降到楼板面。在卷帘的任一侧距卷帘纵深0.5-5m内应设置不少于2只专门用于联动防火卷帘的感温火灾探测器。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]