[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974333":3},{"question":4,"library":29},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":27,"analysis":28},974333,704,2,"多选题","下列方式可以控制排烟风机启动的有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","现场手动启动",true,{"key":16,"text":17,"correct":14},"B","通过火灾自动报警系统自动启动",{"key":19,"text":20,"correct":14},"C","消防控制室手动启动",{"key":22,"text":23,"correct":14},"D","系统中任一排烟阀或排烟口开启时，排烟风机自动启动",{"key":25,"text":26,"correct":14},"E","排烟防火阀在280℃时自行关闭，连锁关闭排烟风机","ABCDE","排烟风机可通过以下方式控制： （1）现场手动启动。 （2）通过火灾自动报警系统自动启动。 （3）消防控制室手动启动。 （4）系统中任一排烟阀或排烟口开启时，排烟风机自动启动。 （5）排烟防火阀在280℃时自行关闭，连锁关闭排烟风机。",{"id":6,"name":30,"category":31,"favorite":32},"中级技能","建筑工程",0]