[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974328":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974328,704,2,"多选题","下列符合排烟风机、补风机的控制方式要求的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","系统中任一排烟阀或排烟口开启时，排烟风机、补风机自动启动",true,{"key":16,"text":17,"correct":14},"B","火灾自动报警系统自动启动",{"key":19,"text":20,"correct":14},"C","消防控制室手动启动",{"key":22,"text":23,"correct":24},"D","排烟防火阀在280℃时应自行关闭，但不能连锁关闭排烟风机和补风机",false,{"key":26,"text":27,"correct":14},"E","现场手动启动","ABCE","依据《建筑防烟排烟系统技术标准》GB51251-2017，排烟风机、补风机的控制方式应符合下列规定： （1）现场手动启动。 （2）火灾自动报警系统自动启动。 （3）消防控制室手动启动。 （4）系统中任一排烟阀或排烟口开启时，排烟风机、补风机自动启动。 （5）排烟防火阀在280℃时应自行关闭，并应连锁关闭排烟风机和补风机。本题答案为ABCE。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]