[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974322":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},974322,704,1,"单选题","下列关于应急照明控制器设置在消防控制室地面上时，下列说法不符合规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","设备面板前的操作距离，单列布置时不应小于1.5m；双列布置时不应小于2m",false,{"key":16,"text":17,"correct":18},"B","在值班人员经常工作的一面，设备面板至墙的距离不应小于4m",true,{"key":20,"text":21,"correct":14},"C","设备面板后的维修距离不宜小于1m",{"key":23,"text":24,"correct":14},"D","设备面盘的排列长度大于4m时，其两端应设置宽度不小于1m的通道","应急照明控制器在消防控制室地面上设置时，应符合下列规定： （1）设备面盘前的操作距离，单列布置时不应小于1.5m；双列布置时不应小于2m； （2）在值班人员经常工作的一面，设备面盘至墙的距离不应小于3m； （3）设备面盘后的维修距离不宜小于1m； （4）设备面盘的排列长度大于4m时，其两端应设置宽度不小于1m的通道。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]