[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974314":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},974314,704,1,"单选题","监控器与电动闭门器、电磁释放器、门磁开关间连接线断路、短路时，防火门监控器应在（ ）s内发出与报警信号有明显区别的声、光故障信号。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","30",{"key":19,"text":20,"correct":14},"C","50",{"key":22,"text":23,"correct":24},"D","100",true,"有下述故障时，监控器应在100s内发出与报警信号有明显区别的声、光故障信号，故障声信号应能手动消除，再有故障信号输入时应能再启动，故障光信号应保持至故障排除： （1）监控器的主电源断电。 （2）监控器与电动闭门器、电磁释放器、门磁开关间连接线断路、短路。 （3）电动闭门器、电磁释放器、门磁开关的供电电源故障。 （4）备用电源与充电器之间的连接线断路、短路。 （5）备用电源发生故障。",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]