[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974285":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},974285,704,1,"单选题","由控制柜按照预先设定逻辑，定期自动控制消防水泵变频运行，并发出各类巡检信号。下列关于消防泵组电气控制柜巡检周期及消防水泵低速转动的时间说法正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","巡检周期不宜大于7d，每台消防水泵低速转动的时间不应少于2min",true,{"key":16,"text":17,"correct":18},"B","巡检周期不宜小于7d，每台消防水泵低速转动的时间不应少于2min",false,{"key":20,"text":21,"correct":18},"C","巡检周期不宜大于7d，每台消防水泵低速转动的时间不应大于2min",{"key":23,"text":24,"correct":18},"D","巡检周期不宜小于7d，每台消防水泵低速转动的时间不应大于2min","消防泵组电气控制柜自动巡检控制：由控制柜按照预先设定逻辑，定期自动控制消防水泵变频运行，并发出各类巡检信号。巡检周期不宜大于7d，每台消防水泵低速转动的时间不应少于2min",{"id":6,"name":27,"category":28,"favorite":29},"中级技能","建筑工程",0]