[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-974195":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},974195,704,2,"多选题","线型光束感烟火灾探测器的设置应符合下列规定：（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","探测器的光束轴线至顶棚的垂直距离宜为0.3m～1.0m",true,{"key":16,"text":17,"correct":14},"B","相邻两组探测器的水平距离不应大于14m",{"key":19,"text":20,"correct":14},"C","探测器至侧墙水平距离不应大于7m，且不应小于0.5m",{"key":22,"text":23,"correct":24},"D","探测器的发射器和接收器之间的距离不宜超过10m",false,{"key":26,"text":27,"correct":24},"E","探测器距地高度不宜超过16m","ABC","线型光束感烟火灾探测器的设置应符合下列规定： （1）探测器的光束轴线至顶棚的垂直距离宜为0.3m～1.0m，距地高度不宜超过20m。 （2）相邻两组探测器的水平距离不应大于14m，探测器至侧墙水平距离不应大于7m，且不应小于0.5m，探测器的发射器和接收器之间的距离不宜超过100m。 （3）探测器应设置在固定结构上。 （4）探测器的设置应保证其接收端避开日光和人工光源直接照射。 （5）选择反射式探测器时，应保证在反射板与探测器间任何部位进行模拟试验时，探测器均能正确响应。",{"id":6,"name":31,"category":32,"favorite":33},"中级技能","建筑工程",0]